| Sign In | Join Free | My components-electronic.com |
|
Brand Name : ZGD
Certification : CE
Place of Origin : China
MOQ : 1 sets
Rated Voltage : 380/400/415 Vac three-phase
Frequency Range : 45-65Hz
Protection Degree : IP20
Efficiency Smart Mode : Up To 98%
Capacity : 8KW 12KW 16KW 24KW 32KW 48KW 64KW 80KW 96KW 128KW 160KW
Power : 10KVA 15KVA 20KVA 30KVA 40KVA 60KVA 80KVA 100KVA 120KVA 160KVA 200KVA
Advance communication
Compatible with TeleNetGuard for remote maintenance; Advanced, multi-platform communication for all operation systems and network environments: Watch & Save 3000 monitoring and shut-down software included, with SNMP agent, for Windows 2008, Vista,2003, XP; Mac OS X, Linux, Novell and most popular Unix operating systems;
The UPS is supplied with a cable for direct connection to the PC(Plug and Play); RS232 double Serial port; Installation slot for an Emergency Power Off (EPO) interface to allow the UPS to be switched off remotely in an emergency; Generator interface: enables resynchronization of the UPS output from a generator supply which may be subject to phase and frequency variations. The interface also enables more economic use of the battery charge.
Expandability:
The units can be connected in parallel up to 8 units to increase power availability or redundancy. The single module or the system can be expanded any time to suit power requirements without influencing the initial investment.
| Model power | ZGD330 10-200KVA | |||||||||||
| 10KVA | 15KVA | 20KVA | 30KVA | 40KVA | 60KVA | 80KVA | 100KVA | 120KVA | 160KVA | 200KVA | ||
| Capacity | 8KW | 12 KW | 16 KW | 24 KW | 32 KW | 48 KW | 64 KW | 80 KW | 96KW | 128 KW | 160 KW | |
| Input | ||||||||||||
| Rated voltage | 380/400/415 Vac three-phase | |||||||||||
| Voltage range | ±20% | |||||||||||
| Frequency range | 45-65Hz | |||||||||||
| Power factor | >0.92with harmonic filter | |||||||||||
| Current harmonic distortion | <5%with harmonic filter | |||||||||||
| Soft Start | 0-100% in10" | |||||||||||
| Bypass Input | ||||||||||||
| Rated voltage | 380/400/415 Vac three-phase | |||||||||||
| Permitted voltage range | ±15%(selectable from ±10% to ±25% from front panel) | |||||||||||
| Rated frequency | 50/60Hz | |||||||||||
| Permitted frequency range | ±2%(selectable from ±1% to ±5% from front panel) | |||||||||||
| Standard features | Back Feed protection; split bypass line | |||||||||||
| Batteries | ||||||||||||
| Type | Maintenance-free lead-acid VRLA AGM / GEL;NICd | |||||||||||
| Battery voltage | 384VDC | 480VDC | ||||||||||
| Maximum recharge current(A) | 0.2×C10 | |||||||||||
| AC ripple voltage | <1% | |||||||||||
| Inverter Output | ||||||||||||
| Number of phases | 3+N | |||||||||||
| Rated voltage(V) | 380Vac | |||||||||||
| Regulation of the output voltage | 380~424Vac phase/neutral(from control panel) | |||||||||||
| Crest factor (Ipeak / Irms) | 3:1 | |||||||||||
| Static stability | ±1% | |||||||||||
| Dynamic stability | ±5% | |||||||||||
| Frequency | 50/60Hz configurable | |||||||||||
| Overload | 110% 125% 150% of the rated current for 5h/10'/1' | |||||||||||
| Frequency stability | ±0.05% on mains failure;±2%(selectable from ±1% to ±5%)with mains supply present | |||||||||||
| Remote signaling | Volt free contacts | |||||||||||
| Remote controls | EPO and Bypass | |||||||||||
| Communication | RS232 + romote contacts | |||||||||||
| Operation temperature | 0ºC/ + 40ºC | |||||||||||
| Relative humidity | <95% non condensing | |||||||||||
| Noise | 54dBA at 1m | 50-65dBA at 1m | ||||||||||
| Protection degree | IP20 | |||||||||||
| Efficiency smart mode | up to 98% | |||||||||||
| Compliance | Safety:EN 62040-1-1(Directive 2006/95/EC); EMC:6200-2(Directive 2004/108/EC) | |||||||||||



|
|
Local Area Network 30KVA Low Frequency Online UPS 3 Phases 380V / 400V / 415V Images |